   ET 200s IM 151-7 CPU是ET 200s 分布式I/O系统的一部分,具有何S7-314相近的功能,其防护等级为IP20,ET 200s IM 151-7 CPU接口模块是一个"智能预处理单元"(1slave),它能让你实现完美的分布式控制。

   一个具有ET 200s IM 151-7 CPU的ET 200s站点能够控制一个工艺单元,而且也可以用作一个单机CPU,通过连接一个主站接口模块ET 200s IM 151-7 CPU可以作为一个DP主站使用。

   此次发布的ET 200s IM 151-7 CPU进一步增加了工作内存,至此,ET 200s IM 151-7 CPU的工作内存已经从24k增加到了96K,这样,使ET 200s IM 151-7 CPU可以完成更加复杂的控制任务,下述为该产品的技术参数。
技术参数的联接内容如下:

Source of technical data: MM

Voltages and currents

Mains/voltage failure jumpering, min.

5 ms

Load voltage L+

Rated value (DC)

24 V

Short-circuit protection

Yes

reverse polarity protection

Yes

permissible range, lower limit (DC)

20,4 V

permissible range, upper limit (DC)

28,8 V

Current consumption

from supply voltage 1L+, max.

250 mA

Power loss, typ.

3,3 W

Current output to backplane bus (DC 5 V), max.

700 mA

Memory

Memory

RAM

integrated

96 KByte

expandable

No

Load memory

pluggable (MMC)

Yes

pluggable (MMC), max.

8 MByte

Data management on MMC (after last programming), min.

10 Jahr(e)

Backup

present

Yes

CPU/blocks

Number of blocks (total)

1024

DB

Number, max.

511

Size, max.

16 KByte

FB

Number, max.

1024

Size, max.

16 KByte

FC

Number, max.

1024

Size, max.

16 KByte

OB

Size, max.

16 KByte

Number of free cycle OBs

1

Number of time alarm OBs

1

Number of delay alarm OBs

1

Number of watchdog interrupts

1

Number of process alarm OBs

1

Number of startup OBs

1

Number of asynchronous error OBs

6

Nesting depth

per priority class

8

additional within an error OB

4

CPU/processing times

for bit operations, min.

0,1 µs

for word operations, min.

0,2 µs

for fixed point arithmetic, min.

2 µs

for floating point arithmetic, min.

3 µs

Times/counters and their remanence

S7 counter

Number

256

of which remanent without battery

adjustable

Yes

lower limit

0

upper limit

255

Remanence

adjustable

Yes

lower limit

0

upper limit

255

Counting range

adjustable

Yes

lower limit

0

upper limit

999

IEC counter

present

Yes

S7 times

Number

256

of which remanent without battery

adjustable

Yes

lower limit

0

upper limit

255

Remanence

adjustable

Yes

lower limit

0

upper limit

255

Time range

lower limit

10 ms

upper limit

9990 s

IEC timer

present

Yes

Data areas and their remanence

remanent data area in total (incl. times, counters, flags), max.

64 KByte

Flag

Number, max.

256 Byte

Remanence available

Yes

Number of clock memories

8

Data blocks

Number, max.

511

Size, max.

16 KByte

Local data

per priority class, max.

510 Byte

Address area

I/O address area

Inputs

2048 KByte

Outputs

2048 KByte

Process image

Inputs

128 Byte

Outputs

128 Byte

Digital channels

Inputs

16336

Outputs

16336

Inputs, of which central

248

Outputs, of which central

248

Analog channels

Inputs

1021

Outputs

1021

Inputs, of which central

124

Outputs, of which central

124

Time

Clock

Hardware clock (real-time clock)

Yes

Clock / Battery backed and synchronized

Yes

Backup time

6 w

Deviation per day, max.

10 s

Operating hours counter

Number

1

remanent

Yes

Clock synchronization

supports

Yes

to MPI, Master

Yes

to MPI, Slave

Yes

in AS, Master

No

in AS, Slave

No

S7 message functions

Number of login stations for message functions, max.

12

Process diagnostic messages

Yes

simultaneously active Alarm-S blocks, max.

40

Test commissioning functions

Status/control

Status/control variable

Yes

Monitoring functions

Number of variables, max.

30

of which status variable, max.

30

of which control variable, max.

14

Forcing

Forcing

Yes

Test and startup functions / Forcing, number of variables, max.

10

Status block

Yes

Single step

Yes

Number of breakpoints

2

Diagnostic buffer

present

Yes

Number of entries, max.

100

adjustable

No

Communication functions

PG/OP communication

Yes

Global data communication

supported

Yes

Number of GD packets, max.

4

Number of GD packets, transmitter, max.

4

Number of GD packets, receiver, max.

4

Size of GD packets, max.

22 Byte

Size of GD packet (of which consistent), max.

22 Byte

S7 basic communication

supported

Yes

Useful data per job, max.

76 Byte

Useful data per job (of which consistent) max.

76 Byte

S7 communication

supported

Yes

as server

Yes

as client

No

Useful data per job, max.

180 Byte

Useful data per job, of which consistent, max.

64 Byte

S5-compatible communication

supported

No

Standard communication (FMS)

supported

No

Number of connections

overall

12

usable for PG communication

11

reserved for PG communication

1

usable for OP communication

11

reserved for OP communication

1

usable for S7 basic communication

10

reserved for S7-Basic communication

0

usable for routing

4

1st interface

isolated

Yes

Stromversorgung an interface (15 to 30 V DC), max.

80 mA

Functionality

MPI

Yes

DP master

No

DP slave

Yes

Point-to-point coupling

No

MPI

Number of connections

12

Services

PG/OP communication

Yes

Routing

Yes

Global data communication

Yes

S7 basic communication

Yes

S7 communication

Yes

S7 communication, as client

No

S7 communication, as server

Yes

Transmission speeds, max.

12 Mbit/s

DP slave

Number of connections

12

Services

PG/OP communication

Yes

Routing

Yes

S7 communication, as client

No

S7 communication, as server

Yes

direct data exchange (cross traffic)

Yes

DPV1

No

Transmission speeds, max.

12 Mbit/s

automatic baud rate search

Yes

Transfer memory

Inputs

244 Byte

Outputs

244 Byte

Address area, max.

32

Useful data per address area, max.

32 Byte

2nd interface

isolated

Yes

Functionality

MPI

No

DP master

Yes

Point-to-point coupling

No

DP master

Number of connections, max.

12

Services

PG/OP communication

Yes

Routing

Yes

Global data communication

No

S7 basic communication

Yes

S7 communication

Yes

S7 communication, as client

No

S7 communication, as server

Yes

equidistance support

Yes

SYNC/FREEZE

Yes

Activation/deactivation of DP slaves

Yes

direct data exchange (cross traffic)

Yes

DPV1

Yes

Transmission speeds, max.

12 Mbit/s

Number of DP slaves, max.

32

Address area

Inputs, max.

2 KByte

Outputs, max.

2 KByte

Useful data per DP slave

Inputs, max.

244 Byte

Outputs, max.

244 Byte

Isochronous mode

Isochronouos mode

No

CPU/programming

Programming language

STEP 7

Yes

LAD

Yes

FUP

Yes

AWL

Yes

SCL

Yes

GRAPH

Yes

Nesting levels

8

User program protection/password protection

Yes

Cycle time monitoring

lower limit

1 ms

upper limit

6000 ms

adjustable

Yes

preset

150 ms

Isolation

between load voltage and all other switching components

Yes

between PROFIBUS DP all all other circuits

Yes

Dimensions and weight

Width

60 mm

Height

119,5 mm

Depth

75 mm

Weights

Weight, approx.

200 g

 