刘军强,陈朝辉 (华能威海电厂,山东威海 264205)
摘要:本文分析了威海电厂凝结水系统运行中存在的能源浪费问题和变频调速的节能原理,探讨了使用的A-B PowerFlex7000中压变频调速装置的结构、保护配置和特点及调试中出现的问题处理。通过节能效果分析,表明该中压变频器在电力工业中具有广阔的应用前景。 关键词:凝结水;变频;A-B;节能 The Application of the A-B Medium Voltage Frequency Converter in Huaneng Weihai Power Plant Liu Jun-qiang,Chen Zhao-hui (Huaneng Weihai Power Plant,Weihai 264205,China) Abstract:This paper analyzes the energy-wasting problem in the operational process of the condensate system in huaneng weihai power plant and the principle of energy saving by the frequency conversion speed regulation.It discusses the structure ,the protection arrangement and the characteristics of the A-B PowerFlex7000 medium voltage frequency conversion speed regulation equipment used in the condensate system,and then it introduces the measures dealt with the problems in the commissioning stage. The results show that the application of the frequency conventer is very beautiful in the electric power industry. Key words:Condensate Water;Frequency Conversion;A-B;Energy Saving 0、引言 2003年以来我国面临着严峻的资源压力,“煤、电、油”全面告急,近八成省份拉闸限电,能源瓶颈正成为制约国民经济可持续增长的最主要因素。泵与风机是全国通用的耗电量较大的设备,在火电厂中应用极广。据统计,全国火电厂的平均厂用电率约为7%~8%,其中泵与风机的耗电量占厂用电的75%左右。目前我国使用的泵与风机的效率,多数比工业先进国家的同类产品的效率低5%~10%;而泵与风机的实际运行效率普遍比工业先进国家低10%~30%[1]。因此积极开展泵与风机的节能降耗,对于促进国民经济持续发展、缩小与工业发达国家的差距,提高电力企业经济效益,增强市场竞争力,都具有现实和深远的意义。 1、设备概况及存在问题 华能威海电厂二期2×300MW机组为国产引进型N300-16.7/538/538中间再热凝汽式汽轮机组;凝结水泵为沈阳水泵厂生产9LDTNA-4型,电机为YLS560型,额定功率1000kW,电压6000V,电流114A,转速1486r/min。机组正常运行时,两台凝结水泵一台运行,一台备用。当运行泵故障时,备用泵自启并投入运行。凝结水通过凝结水泵升压后,流经各低压加热器和凝结水主、副调节阀最后到达除氧器。凝结水主、副调节阀的开度由除氧器实际水位和给定值、给水流量和凝结水流量构成的除氧器水位控制回路(单冲量或三冲量)调节控制。机组正常运行时凝结水主、副调节阀的开度如表1所示。由表1可以看出凝结水泵长期处于极度节流状态,造成能量大量浪费,效率极低。